Fail-Safe Modules
7.8 1 F-RO DC24V/AC24..230V/5A Digital Electronic Module
Terminal
9
10
11
12
A12
A11
13
14
15
16
A16
A15
Wire these terminals in parallel if high currents are generated at OUT 1 or OUT 2 (≥ 50% of
the rated current of the respective output channel):
• For OUT 1: Terminals 9/10 and 13/14
• For OUT 2: Terminals 11/12 and 15/16
Otherwise, high current loads may cause the terminals to heat up.
180
Designation
NO contact, channel 0 for fail-safe switching of load 1
OUT 1
OUT 1
OUT 2
NO contact, channel 1 for fail-safe switching of load 2
OUT 2
AUX 1
At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3
to A16 for any PE connection.
Individual grouping of load current supplies is supported.
AUX 1
At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3
to A16 for any PE connection.
Individual grouping of load current supplies is supported.
OUT 1
NO contact, channel 0 for fail-safe switching of load 1
OUT 1
OUT 2
NO contact, channel 1 for fail-safe switching of load 2
OUT 2
AUX 1
At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3
to A16 for any PE connection.
Individual grouping of load current supplies is supported.
AUX 1
At TM-E...46-A1: AUX 1 bus implemented. Connection to terminals A3
to A16 for any PE connection.
Individual grouping of load current supplies is supported.
CAUTION
ET 200S Distributed I/O System - Fail-Safe Modules
Installation and Operating Manual, 08/2008, A5E00103686-07