PROBLEM
Radiators
cold
in
winter
High
variability
of
temperature
of
domestic hot water
Little domestic hot
water is provided
Hot
water
is
not
provided
ATTENTION!
The operations
specialised MCZ personnel.
The manufacturer refuses to accept any responsibility
and the guarantee lapses if this condition is not
respected.
Problems / Causes / Solutions
PELLET STOVES
INSTALLATION AND USE MANUAL
POSSIBLE CAUSES
1. Room thermostat (local or remote)
set too low. If remote thermostat,
check if it is defective.
2. Circulator does not run because
blocked.
3. Circulator does not run.
4. Radiators have air in them
1. Water flow rate too low.
1. Insufficient mains pressure
2. Tap or mixer clogged with limescale
3. Water group clogged
1. Circulator (pump) blocked
in italics
must be carried out by
REMEDY
1.
Set
to
higher
replace. (if remote)
2. Free up the circulator by removing
the plug and turning the shaft with a
screwdriver.
3. Check the electrical connections of
the circulator; replace if necessary.
4. Vent the radiators
1. Increase
the
(minimum 3 litres per minute)
1. Check
the
calibration
pressure reducer.
2. Install and autoclave
3. Check and clean
4. Clean or replace the plate heat
exchanger
1. Free the circulator (pump)
Technical service - Rights reserved MCZ S.p.A. - Reproduction prohibited
Chapter 6
61
page
temperature
or
water
flow
rate
of
the