F214
RR Torque Reference 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input
at the RR input terminal:
• Program  Utility Group  Frequency Mode 1  RR.
• Program  Utility Group  Command Mode  Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from
the RR input terminal:
• Set
RR Torque Reference 1
• Set
RR Reference 1
(F210) — the input analog signal level that corresponds
to the torque setting at
• Set
RR Torque Reference 2
• Set
RR Reference 2
(F212) — the input analog signal level that corresponds
to the frequency setting at
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
Once set, as the RR input voltage changes, the output torque of the ASD will vary
in accordance with the above settings.
This parameter sets
RR Torque Reference 1
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
RR Torque Reference 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
This parameter sets
RR Torque Reference 2
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
See
RR Torque Reference 1
Q9 ASD Installation and Operation Manual
(F214).
RR Torque Reference
1.
(F215).
RR Torque Reference
2.
and is the output torque value that is
RR Reference 1
when operating in the Torque
and is the output torque value that is
RR Reference 2
when operating in the Torque
for more information on this setting.
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
Direct Access Number — F215
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
F215
89