Cable/Terminal Specifications

Installation should conform to the 2008 National Electrical Code Article 110 (NEC
Installations), all regulations of the Occupational Safety and Health Administration, and any other
applicable national, regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the Q9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the Q9 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the Q9 ASD and Do
Not include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 17. 230-Volt Q9 ASD Cable/Terminal/Torque Specifications.
Wire/Cable Size
Model
Number
VT130Q9U
Input/Output Power
Recommended
2010
14
2015
14
2025
14
2035
14
2055
10
2080
8
2110
8
2160
6
2220
4
2270
3
2330
2
2400
1/0
2500
2/0
2600
4/0
Q9 ASD Installation and Operation Manual
Lug Size Range
AWG or kcmil
Wire-Size/Lug-Capacity for
Input/Output Power
Maximum
3Ø-Input
10
10
10
14 to 10
10
10
8
12 to 8
8
10 to 4
3
8 to 2
3
3
4 to 1/0
2
4/0
4/0
2 to 300
4/0
) (Requirements for Electrical
Terminal
Board Wire
Size
In-Lbs./N·m
TB1 – 4
3Ø-Output
Terminals
20
(3-core shield)
Torque to 5.3/0.6
Torque
3Ø-Input 3Ø-Output
12.4/1.4
26.6/3
47.8/5.4
212/24
360/41
213