Lead Length Specifications - Toshiba Q9 Installation And Operation Manual

Asd
Table of Contents

Advertisement

Lead Length Specifications

Adhere to the NEC and any local codes during the installation of ASD/motor systems. Excessive lead
lengths may adversely effect the performance of the motor. Special cables are not required. Lead lengths
from the ASD to the motor in excess of those listed in
of the ASD.
Table 1
Model
230-Volt
460-Volt
Contact the Toshiba Customer Support Center for application assistance when using lead lengths in excess
of those listed.
Exceeding the peak voltage rating or the allowable thermal rise time of the motor insulation will reduce
the life expectancy of the motor.
When operating in the Vector Control mode the carrier frequency should be set to 2.2 kHz or above.
18
lists the suggested maximum lead lengths for the listed motor voltages.
Table 1. Lead Length Recommendations.
PWM Carrier
NEMA MG1 Part 31
Frequency
Compliant Motors
All
< 5 kHz
≥ 5 kHz
Table 1
may require filters to be added to the output
NEMA MG1 Part 30
1000 feet
600 feet
300 feet
Q9 ASD Installation and Operation Manual
Compliant Motors
450 feet
200 feet
100 feet

Hide quick links: