EOI Display
*DC Over-Volts
DC Bus Voltage Exceeds Specifications.
Under-Voltage Condition at the 5, 15, or
*DC Under-Volts
the 24 VDC supply.
Emergency Off
Emergency Off.
Heavy Load
Motor/ASD Over Loaded.
Light Load
Light Load.
Lower Limit
Lower-Limit Time.
Under-Voltage (Main Circuit Power
Main Under-Volts
Supply).
Motor Overload
Motor Overload.
Note:
* Reset ignored if active.
198
Table 11. Alarms (Continued)
Fault Description
Possible Cause
• ASD is attempting to start into a spinning motor
after a momentary power loss.
• Incoming commercial power voltage level is
above the specified range.
• Deceleration time is too short.
• Voltage spikes at the 3-phase input; install
inductive filter.
• Over-Voltage Stall feature is turned off.
• System is regenerating.
• Load fluctuations.
• Defective control board.
• Excessive load on power supply.
• Low input voltage.
• Stop-Reset pressed twice at the EOI.
• E-OFF command received remotely.
• Acceleration time is too short.
• ASD is improperly matched to the application.
• Excessive load.
• ASD is improperly matched to the application.
• Parameter
F256
adjustment required.
• 3-phase input voltage low.
• Defective control board.
• Excessive load on power supply.
• Under-Voltage/Ridethrough settings require
adjustment.
• V/f setting require adjustment.
• Motor is locked.
• Continuous operation at low speed.
• Motor is improperly matched to the load.
Q9 ASD Installation and Operation Manual