F686
AM Bias Adjustment
Program  AM/FM
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at
F670
operation.
See
F670
for more information on this setting.
MON 1 Voltage/Current Output Switching
No Path — Direct Access Only
This parameter is used to set the output signal type of the MON1 output terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
MON 1 Output Gradient Characteristic
No Path — Direct Access Only
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON 1 Bias Adjustment
No Path — Direct Access Only
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter
a zero output.
See parameter
F672
for more information on this setting.
MON 2 Voltage/Current Output Switching
No Path — Direct Access Only
This parameter is used to set the output signal type of the MON2 output terminal.
See parameter
F674
for more information on this setting.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
Q9 ASD Installation and Operation Manual
to zero and then set this parameter to zero for proper
F672
to zero and then set this parameter to
Direct Access Number — F686
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
Direct Access Number — F688
Parameter Type — Selection List
Factory Default — 0 – 10 V
Changeable During Run — Yes
Direct Access Number — F689
Parameter Type — Selection List
Factory Default — Plus (Positive
Gradient)
Changeable During Run — Yes
Direct Access Number — F690
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F691
Parameter Type — Selection List
Factory Default — 0 – 10 V
Changeable During Run — Yes
F691
145