F638
PTC2 Thermal Selection
No Path — Direct Access Only
This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 2. A thermistor is connected from TH1+ to
TH1- of TB4 on the Expansion IO Card Option 2.
Should the thermistor resistance reading fall below 50Ω because of an over-
temperature condition or exceed 3000Ω because of an open circuit an External
Thermal Fault (OH2) will be incurred.
Note:
While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8kΩ from an
over-temperature condition. An Auto-Restart will not be initiated
subsequent to an External Thermal Trip (OH2). A manual restart
will be required in the event of an OH2 trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Braking Resistance Overload Time (10x rated torque)
No Path — Direct Access Only
This parameter sets the time that the braking resistor is allowed to sustain and
overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load or for loads that
require a long deceleration time.
Step-Out Current Detection Level
Program  Protection
This parameter is used with synchronous motor applications only.
Contact the Toshiba Customer Support Center for information on this
parameter.
Step-Out Current Detection Time
Program  Protection
This parameter is used with synchronous motor applications only.
Contact the Toshiba Customer Support Center for information on this
parameter.
Q9 ASD Installation and Operation Manual
Direct Access Number — F638
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F639
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 150
Units — %
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 25.0
Units — Seconds
F641
137