F638
PTC2 Thermal Selection
No Path — Direct Access Only
This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 2. A thermistor is connected from TH1+ to
TH1- of TB4 on the Expansion IO Card Option 2.
Should the thermistor resistance reading fall below 50Ω because of an over-
temperature condition or exceed 3000Ω because of an open circuit an External
Thermal Fault (OH2) will be incurred.
Note:
While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8kΩ from an
over-temperature condition. An Auto-Restart will not be initiated
subsequent to an External Thermal Trip (OH2). A manual restart
will be required in the event of an OH2 trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Braking Resistance Overload Time (10x rated torque)
No Path — Direct Access Only
This parameter sets the time that the braking resistor is allowed to sustain and
overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load or for loads that
require a long deceleration time.
Step-Out Current Detection Level
Program Protection
This parameter is used with synchronous motor applications only.
Contact the Toshiba Customer Support Center for information on this
parameter.
Step-Out Current Detection Time
Program Protection
This parameter is used with synchronous motor applications only.
Contact the Toshiba Customer Support Center for information on this
parameter.
Q9 ASD Installation and Operation Manual
Direct Access Number — F638
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F639
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 150
Units — %
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 25.0
Units — Seconds
F641
137