Toshiba Q9 Installation And Operation Manual page 86

Asd
Table of Contents

Advertisement

F133
OUT3 Terminal
Program  Output Terminals
This parameter is used to set the functionality of the OUT3 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This setting assigns the function of the programmable OUT3 terminal to any of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 1 Option Board (P/N ETB003Z) is
required to use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for more
information on the function of this terminal.
OUT4 Terminal
Program  Output Terminals
This parameter is used to set the functionality of the OUT4 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This setting assigns the function of the programmable OUT4 terminal to any of
the user-selectable functions listed in
Note:
The Expansion IO Card Option 1 Option Board (P/N ETB003Z) is
required to use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for more
information on the function of this terminal.
R1 Terminal
Program  Output Terminals
This parameter is used to set the functionality of the R1 discrete output terminal.
In addition, this input terminal must be specified as Normally Open or Normally
Closed.
This setting assigns the function of the programmable R1 terminal to any of the
user-selectable functions listed in
Note:
The Expansion IO Card Option 1 Option Board (P/N ETB003Z) is
required to use this terminal.
See the Expansion IO Card Option 1 Instruction Manual (P/N 58685) for more
information on the function of this terminal.
76
Table 7 on pg.
190.
Table 7 on pg.
190.
Table 7 on pg.
190.
Direct Access Number — F133
Parameter Type — Selection List
Factory Default — Always OFF
Changeable During Run — No
Direct Access Number — F134
Parameter Type — Selection List
Factory Default — Always OFF
Changeable During Run — No
Direct Access Number — F135
Parameter Type — Selection List
Factory Default — Always OFF
Changeable During Run — No
Q9 ASD Installation and Operation Manual