Toshiba Q9 Installation And Operation Manual page 27

Asd
Table of Contents

Advertisement

Figure 4. The Grounding Capacitor
Switch is used on typeforms — 200-volt
0.5 HP to 10 HP and the 25 and 30 HP/
460-volt 1.0 HP to 250 HP.
The value may be set to Maximum
(default setting) or to Zero by pushing or
pulling the switch actuator, respectively.
Figure 5. The Grounding Capacitor
Switch is used on typeforms — 200-volt
15 HP to 20 HP and the 40 HP to 60 HP/
460-volt 30 HP to 100 HP.
The value may be set to Large (default
setting) or Small by pushing or pulling
the switch actuator, respectively.
Figure 6. The Grounding Capacitor Bar
is used on typeforms — 200-volt 75 HP
and the 100 HP/460-volt 125 HP and the
150 HP. The value may be set to Large
or Small (default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. The Grounding Capacitor
Screw is used on typeforms — 460-volt
175 HP and above.
The value may be set to Large or Small
(default setting) by placing the screw in
the A position or by placing the screw in
the B position, respectively.
Q9 ASD Installation and Operation Manual
17