F672
MON1 Terminal Meter Selection
No Path — Direct Access Only
This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in
on pg.
189.
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 Option Board (P/N ETB004Z) is
required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for more
information on the function of this terminal.
MON1 Terminal Setup Parameters
F672
— Output Function
F673
— Terminal Meter Adjustment
F688
— Voltage/Current Output Switching
F689
— Output Gradient Characteristic
F690
— Bias Adjustment
MON1 Terminal Adjustment
No Path — Direct Access Only
This parameter is used to set the gain of the MON1 output terminal and is used in
conjunction with the settings of parameter F672.
See parameter
F672
for more information on this setting.
MON2 Terminal Meter Assignment
No Path — Direct Access Only
This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in
on pg.
189.
The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 Option Board (P/N ETB004Z) is
required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for more
information on the function of this terminal.
MON2 Terminal Setup Parameters
F674
— Terminal Meter Assignment
F675
— Terminal Meter Adjustment
F691
— Voltage/Current Output Switching
F692
— Output Gradient Characteristic
F693
— Bias Adjustment Set Zero Level
142
Direct Access Number — F672
Parameter Type — Selection List
Factory Default — Output Voltage
Changeable During Run — Yes
Table 6
Direct Access Number — F673
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F674
Parameter Type — Selection List
Factory Default — Comp. Frequency
Changeable During Run — Yes
Table 6
Q9 ASD Installation and Operation Manual