MON 2 Output Gradient Characteristic
No Path — Direct Access Only
This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON 2 Bias Adjustment
No Path — Direct Access Only
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON2 terminal.
Set the assigned function of parameter
a zero output.
See parameter
F674
for more information on this setting.
Parameter Write Lockout
No Path — Direct Access Only
This parameter Enables/Disables the Run and Stop keys.
Settings:
0 — Enabled
1 — Disabled
Display Units for Voltage and Current
Program  Utility Group
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Frequency Display Multiplier
Program  Utility Group
This parameter provides a multiplier for the displayed speed value shown on the
front panel display of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units
Example: An output frequency of 100 Hz would be displayed as 50 Hz if
using a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters are not affected by this
(i.e.
setting
, F364, F365, F367, and F368).
146
F674
to zero and then set this parameter to
(i.e.
, Units/Time).
Direct Access Number — F692
Parameter Type — Selection List
Factory Default — Plus (Positive
Gradient)
Changeable During Run — Yes
Direct Access Number — F693
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F700
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00 (OFF)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
Q9 ASD Installation and Operation Manual