F740
Trace Selection
No Path — Direct Access Only
In conjunction with parameter
store 4 ASD output waveform data points. The data may be read and stored as a
function of a trip (At Trip) or it may be initiated by the activation of a discrete
terminal activation (At Trigger).
The table below lists the items that may selected for the data read/store function.
Select At Trip at this parameter to read/store the value of the item selected from
the table below in the event of a trip.
Select At Trigger at this parameter and set and activate a discrete input terminal
to Trace Back Trigger Signal to initiate the At Trigger read/store of the item
selected from the table below.
The duration of the read/store cycle for the selected data is set at parameter F741.
A communications device is required to use this parameter and a PC is used to
store the acquired data. The Q9 ASD supports the following communications
protocols: RS485 (MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol,
CC-Link, ProfiBus, and DeviceNet (Refer to the manual of each protocol type for
more information).
Settings:
0 — None
1 — At Trip
2 — At Trigger
Once enabled at this parameter, the following monitored items (data points) may be
selected for the read/store function at
Output Frequency
Frequency Reference
Output Current
DC Bus Voltage
Output Voltage
Compensated Frequency
Speed Feedback (Realtime)
Speed Feedback (1 Sec Filter) Option V/I Input
Torque
Torque Command
Torque Current
Excitation Current
150
F741
– F745, this parameter is used to monitor and
F742
– F745.
PID Feedback Value
FM Output
Motor Overload Ratio AM Output
ASD Overload Ratio 100% Meter Adjust Value
DBR Overload Ratio
Data From Communication
(Not Used)
DBR Load Ratio (Not
250% Meter Adjust Value
Used)
Input Power
Input Watt Hour
Output Power
Output Watt Hour
Gain Display
My Function Monitor 1
RR Input
Without Sign
My Function Monitor 2
V/I Input
Without Sign
My Function Monitor 3
RX Input
With Sign
My Function Monitor 4
RX2 (AI1) Input
With Sign
Direct Access Number — F740
Parameter Type — Selection List
Factory Default — At Trip
Changeable During Run — Yes
Q9 ASD Installation and Operation Manual