F235
PG Frequency 1
Program  Frequency Settings
This parameter is used to set the speed of the PG input terminals when the PG
terminal is used as the control input.
This parameter sets
PG Frequency 1
the setting of PG Reference 1.
See PG Reference 1 (F234) for further information on this setting.
PG Reference 2
Program  Frequency Settings
This parameter is used to set the direction and speed of the PG input terminals
when the PG terminals are used as the control input.
This parameter sets the PG input signal that is associated with
This value is entered as 0% to 100% of the PG input signal range.
See PG Reference 1 (F234) for further information on this setting.
PG Frequency 2
Program  Frequency Settings
This parameter is used to set the direction and speed of the PG input terminals
when the PG terminal are used as the control input.
This parameter sets
PG Frequency 2
the setting of PG Reference 2.
See PG Reference 1 (F234) for further information on this setting.
Startup Frequency
Program  Special Controls
The output of the ASD will remain at 0.0 Hz until the programmed speed value
exceeds this setting during startup. Once exceeded during startup, the output
frequency of the ASD will accelerate to the programmed setting.
Output frequencies below the Startup Frequency will not be output from the
ASD during startup. However, once reaching the Startup Frequency, speed
values below the Startup Frequency may be output from the ASD.
If the setting of this parameter results in an over-current condition at startup,
reduce the setting of this parameter to a value less than the rated slippage of the
motor.
If zero-speed torque is required, set this parameter and
This setting will override the setting of
This parameter setting is used during a Jog as the Lower-Limit Frequency (see
F260).
Q9 ASD Installation and Operation Manual
and is the frequency that is associated with
PG Frequency
and is the frequency that is associated with
F243
to 0.0 Hz.
F244
if this setting has a higher value.
Direct Access Number — F235
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F236
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
2.
Maximum — 100
Units — %
Direct Access Number — F237
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F240
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F240
97