Toshiba Q9 Installation And Operation Manual page 104

Asd
Table of Contents

Advertisement

F224
RX2 (AI1) Reference 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
This parameter sets the RX2 (AI1) input level that is associated with
Frequency 2
when operating in the Speed control mode.
This value is entered as -100% to +100% of the RX2 (AI1) input signal range.
See RX2 (AI1) Reference 1 (F222) for more information on this setting when
used for Speed control.
RX2 (AI1) Frequency 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets
RX2 (AI1) Frequency 2
with the setting of
RX2 (AI1) Reference 2
mode.
See RX2 (AI1) Reference 1 (F222) for more information on this setting.
94
RX2 (AI1)
and is the frequency that is associated
when operating in the Speed Control
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Q9 ASD Installation and Operation Manual
F225

Hide quick links:

Advertisement

Table of Contents
loading