F173
Motor Overload Protection Level 2
No Path — Direct Access Only
The Motor 2 Overload Protection Level parameter specifies the motor overload
current level for motor number 2. This value is entered as either a percentage of
the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps (A/V) or it may
be set as a percentage of the ASD rating. The name-plated FLA of the motor may
be entered directly when Amps is selected as the unit of measurement (see
to change the display unit).
The Motor 2 Overload Protection Level setting will be displayed in Amps if the
EOI display units are set to A/V rather than %.
V/f 5-Point Setting Frequency 1
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 1 setting establishes the frequency that is to
be associated with the voltage setting of
The V/f 5-point settings define a volts per hertz relationship for the startup output
of the ASD.
To enable this function, set the V/f Pattern (F015) selection to the V/f 5-Point
Curve setting.
V/f Curves may be useful in starting high inertia loads such as rotary drum
vacuum filters.
Q9 ASD Installation and Operation Manual
F191
(V/f 5-Point Setting Voltage 1).
Direct Access Number — F173
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 100
Units — %
F701
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F190
79