F647
Backup Option Selection
No Path — Direct Access Only
This parameter sets the ASD disposition in the event that an Under-torque
condition exists for longer than the time setting of F654.
Settings:
0 — Do Nothing
1 — Alarm
2 — Trip
Forced Fire Speed
Program  Special Controls
This parameter is used to enable the Forced Fire Speed function. The Forced
Fire Speed function runs
Preset Speed 15
Preset Speed 15
must be configured to use the Forced Fire Speed function.
Settings:
0 — Enabled
1 — Disabled
Under-Torque at Constant Speed Disposition
No Path — Direct Access Only
This parameter sets the ASD disposition in the event that an Under-Torque
condition exists for longer than the time setting of F654.
Settings:
0 — Do Nothing
1 — Alarm
2 — Trip
Under-Torque Level While ASD-Driven
No Path — Direct Access Only
When enabled at parameter
this setting is used to set a low-torque threshold minimum level that must exist for
the duration of the time setting of parameter
disposition of the parameter
Under-Torque Level During Regeneration
No Path — Direct Access Only
When enabled at parameter
set a low-torque threshold minimum level that must exist for the duration of the
time setting of parameter
F654
parameter
F651
setting.
Q9 ASD Installation and Operation Manual
in the event of an emergency.
F651
and while the motor is being driven by the ASD,
F654
to activate the Under-Torque
F651
setting.
F651
and during regeneration, this setting is used to
to activate the Under-Torque disposition of the
Direct Access Number — F647
Parameter Type — Selection List
Factory Default — Do Nothing
Changeable During Run — No
Direct Access Number — F650
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — No
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Do Nothing
Changeable During Run — No
Direct Access Number — F652
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F653
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — No
Minimum — 0.00
Maximum — 250.0
Units — %
F653
139