G102 Max Input & G142 Max Input; G103 Ref @Min In & G143 Ref @ Min In; G104 Ref @Max In & G144 Ref @ Max In - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

MSC-3 Start Up
• Press  to accept the new value OR
• Press ESC to abandon the value change.
If the G100 Input Type is configured for > Volts then G101 MIN input will be displayed with units of
volts (V) otherwise G101 MIN input will be displayed with units of milliamps (mA). In either case the
minimum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.
G102 MAX Input & G142 MAX Input
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
If the G100 Input Type is configured for > Volts then G102 MAX input will be displayed with units of
volts (V) otherwise G102 MAX input will be displayed with units of milliamps (mA). In either case the
maximum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.
G103 Ref @MIN in & G143 Ref @ MIN in
Range: -100.0...100.0 % of C03 MAX Hz
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
Regardless of how the analogue input is configured the minimum reference for input spanning is
determined by this parameter. The G103 Ref @MIN in parameter corresponds to the
G101 MIN input to define the input spanning configuration. See the Analogue Inputs and Spanning
feature for details.
G104 Ref @MAX in & G144 Ref @ MAX in
Range: -100.0...100.0 % of C03 MAX Hz
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
106
G102 MAX input
>
10.0 V
G103 Ref @MIN in
0.0%
G04 Ref @MAX In
100.0%
IM00120
IM00120

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents