Analog Values; Accumulators - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

Analog Values

Instance ID Object Name
AV0
Cpreset
AV1
Preset
AV2
Accel time
AV3
Decel time
AV4
S time
AV5
Current limit
AV6
AR allowed
AV7
AR clear time
AV8
Under speed
AV9
Over speed
AV10
Speed
AV11
Speed
AV12
Frequency
AV13
Load
AV14
Current
AV15
DC Volts
AV16
Power
AV17
AC Volts
AV18
Temp
AV19
I2T used

Accumulators

Instance ID
Object Name
ACC0
kWh
ACC1
Hours
Present Value Access:
R = Read only
W = Writeable
C = Commandable
Commandable objects support priority arrays and relinquish defaults.
Description
Speed reference
Preset analog value for general use
Acceleration time 0 - max speed
Deceleration time max speed - 0
S characteristic of acceleration and
deceleration
Current limit
Number of auto restarts allowed
Running time without trip to clear
auto start counter
Set point for under speed alarm
Set point for over speed alarm
Motor speed
Motor speed
VFD output frequency
Load torque
Motor phase current
DC bus voltage
Power to motor
AC Line Voltage
Heatsink temperature
Amount of the thermal capacity of
the motor used
Description
kWh consumed by the motor
Run Number of motor operation
hours
IM00120
IM00120
MSC-3 Instruction Manual
Units
Present Value
Access
%
C
%
C
seconds
C
seconds
C
seconds
C
Amps
C
-
C
minutes
C
%
C
%
C
RPM
R
%
R
Hz
R
%
R
Amp
R
Volt
R
kW
R
Volt
R
Degree C
R
%
R
Units
Present Value
Access
kWh
R
hours
R
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents