Binary Values - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

MSC-3 Start Up

Binary Values

Instance ID Object Name
BV0
Run fwd
BV1
Run rev
BV2
Reset
BV3
ESO
BV4
Remote
BV5
Enabled
BV6
Switching
BV7
Powered up
BV8
Buscharged
BV9
Ramping to
stop
BV10
Coasting
BV11
ARfailed
BV12
OPTSC
BV13
Overvoltage
BV14
Overcurrent
BV15
DC low
BV16
Power fail
BV17
Over temp
BV18
I2t trip
BV19
Tripped
BV20
Vlimit
BV21
Climit
BV22
Zero speed
BV23
At speed
BV24
Run
Present Value Access:
R = Read only
W = Writeable
C = Commandable
Commandable objects support priority arrays and relinquish defaults.
122
Description
Run FWD Command Active
Run REV Command
Active
Reset Command
RESETTING
ESO Mode
ESO ACTIVE
Remote Status
Remote
Enable Status
Enabled
Switching Status
Switching
Power Up Status
Powered Up
Bus Charged Status
Bus Charged
Ramping Status
Ramping to Stop
Coasting Status
Coasting
Auto Restart Status
AUTO RESTART
FAILED
Output Short Status
OUTPUT SHORT
Over Voltage Trip
OVERVOLTAGE
Over Current Trip
OVERCURRENT
DC Low Trip
DC LOW
Power Fail Trip
POWER FAIL
Over Temp Trip
OVERTEMPERATURE
I2t Trip
I2t TRIP
Trip Status
TRIPPED
Voltage Limit
Active
Current Limit
Active
At Zero Speed
Zero Speed
At Speed Status
At Commanded speed
Run Status
Running
IM00120
IM00120
Active Text
Inactive Text
Inactive
Inactive
Inactive
Inactive
Local
Disabled
Output Off
Warming Up
Charging
Clear
Clear
Ready
Clear
Clear
Clear
Clear
Clear
Clear
Clear
Clear
Inactive
Inactive
Turning
Speed
Changing
Stopped
Present
Value
Access
C
C
W
C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents