MSC-3 Start Up
If the G020 AN IN mode is configured for > Volts then G021 MIN input will be displayed with units of
volts (V) otherwise G021 MIN input will be displayed with units of milliamps (mA). In either case the
minimum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.

G022 MAX Input

Range: 0.0...10.0 V or 0.0 to 20 mA
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
If the G020 AN IN mode is configured for > Volts then G022 MAX input will be displayed with units of
volts (V) otherwise G022 MAX input will be displayed with units of milliamps (mA). In either case the
maximum input for spanning is determined by this parameter. See the Analogue Inputs and Spanning
feature for details.

G023 Ref @MIN in

Range: -100.0...100.0 % of C03 MAX Hz
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
Regardless of how the analogue input is configured the minimum reference for input spanning is
determined by this parameter. The G023 Ref @MIN in parameter corresponds to the
G021 MIN input to define the input spanning configuration. See the Analogue Inputs and Spanning
feature for details.

G024 Ref @MAX in

Range: -100.0...100.0 % of C03 MAX Hz
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
96
G022 MAX Input
>
10.0V
G023 Ref @MIN In
0.0%
G024 Ref @MAX In
100.0%