G043 Rl2 Toff; G05 Rly Configs; G050 Under Speed; G051 Over Speed - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

• Press ESC to abandon the value change.
In some instances it is desirable to delay the activation of a relay to assist with signal interlock for
example. This parameter sets the relay on delay for relay #2

G043 RL2 TOFF

Range: 0...600 seconds
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
In some instances it is desirable to delay the de- activation of a relay to assist with signal interlock for
example. This parameter sets the relay off delay for relay #2

G05 RLY CONFIGS

Several of the relay functions require parameters for their operation. Parameters include under and over
speed thresholds and calibration points for the percentage load warning output function.

G050 UNDER SPEED

Range: 0.0...100.0 % of (C03 MAX Hz)
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
The G050 UNDER SPEED parameter is a motor frequency compare threshold. When the motor
frequency is below this value, the relay will energise. For example the > UNDER SPEED relay function
has been assigned to relay #2 (G040 RELAY #2 = UNDER SPEED) and G050 UNDER SPEED is set to
20%. When the output frequency goes below 20%, relay 2 will energise.

G051 OVER SPEED

Range: 0.0...100.0 % of (C03 MAX Hz)
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
G043 RL2 TOFF
0 secs
G050 UNDER SPEED
20.0%
G051 OVER SPEED
80.0%
IM00120
IM00120
MSC-3 Instruction Manual
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents