MSC-3 Start Up
• Press  once to begin input selection.
• Use the ▲ / ▼ buttons to select volts or milliamps input operation.
• Press  to confirm the choice. ESC to abandon the change.
The analogue output is configurable for voltage or milliamp output. This selection will configure the
output circuitry for either voltage input or current (mA) output without any need to access MSC-3
hardware. See the Extended Feature Analogue Output feature for details.
G111 AO Source & G151 AO Source
Available choices:
Signal Choices
Description
SPEED
Estimated motor speed, units of "rpm".
I2t
Thermal overload level, units of "Amps".
% LOAD
Motor loading, units of "%".
CURRENT
Motor current, units of "Amps".
POWER
Inverter output power, units of "kW".
• Press  once to begin input selection.
• Use the ▲ / ▼ buttons to select the output signal source.
• Press  to confirm the choice. ESC to abandon the change.
G112 Signal min & G152 Signal min
Range: 0.0...1000.0 in the units of the selected signal
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
The G112 Signal MIN parameter is the minimum signal input used for spanning and has units of the
signal source selected by G111 AN OUT sel. See the Analogue Outputs feature for details.
G113 Signal max & G153 Signal max
Range: 0.0...1000.0 in the units of the selected signal
• Press  to edit the value.
108
G111 AO Source
>
0.0 V
G112 Signal MIN
>
0.0
G113 Signal MAX
>
1000.0
IM00120