MSC-3 Start Up
Error:
Function code
Exception code
Function Code 07: Read Exception Status
Request:
Function code
Response:
Function code
Output data
Function Code 08: Diagnostics, Sub Codes 0, 2, 10...18, 20
Request:
Function code
Sub function
Data
Response:
Function code
Sub function
Data
Error:
Function code
Exception code
Function Code 15: Write Multiple Coils
128
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
8
2 bytes
0, 0 Return query (request) data
0, 2 Return diagnostic register
0, 10 Clear counters and diagnostic register
0, 11 Return network message count
0, 12 Return network communication error count
0, 13 Return network exception error count
0, 14 Return slave message count
0, 15 Return slave no response count
0, 16 Return slave NAK count
0, 17 Return slave busy count
0, 18 Return network character overrun count
0, 20 Clear overrun counter and flag
2 bytes
Data for MSC-3 MODBUS diagnostics
1 byte
2 bytes
2 bytes
1 byte
1 byte
IM00120
IM00120
134 (128+function code, 0x86)
1, 2 or 3
7
7
0 to 255
8
0,2,10...18,20
136 (128+function code, 0x88)
1 or 3