G03 Rl1; Relay Output Functions; G030 Rl1 Signal - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

MSC-3 Start Up
If the G020 Input Type is configured for > Volts then G026 Lo Compare Level will be displayed with
units of volts (V) otherwise G026 Lo Compare Level will be displayed with units of milliamps (mA). In
either case the low level compare threshold is determined by this parameter. When the input falls below
this level, the compare output will be true (high). See the Analogue Inputs and Spanning feature for
details.

G03 RL1(15,16)

As standard the MSC-3 is equipped with 2 relays each with a single normally open contact. This menu
allows configuration of Relay #1 (RL1 on the terminal strip). Configuration parameters include: a relay
signal function selection, relay signal inversion option and delay on and off interval specifications.

Relay Output Functions

Function
RUN
TRIP
ESO
PROOF
ZERO SPD
AT SPEED
UNDER SPD
OVER SPD
ON
OPT ALARM
A/R FAIL
FWD
REV
ENABLED
I2t TRIP
OVER TEMP
LOAD WARN
AUX_PWR
Hi Al(10, 11)
Lo Al(10, 11)
Hi Al(39, 40)
1
Lo Al(39, 40)
1
Hi Al(59, 60)
1
Lo Al(59, 60)
1
T1 Output
T2 Output
Only visible if extended features card fitted
1

G030 RL1 Signal

Available choices:
98
Indication when energised
Running either forward or reverse
A trip has stopped the output of the drive
Running in Essential Services Override
Enabled and not tripped
The motor is at zero speed
The motor speed is equal to the reference speed
The motor speed is below the G050 UNDER SPEED threshold
The motor speed is above the G051 OVER SPEED threshold
The relay is energised
The drive output current is more than 12.5% of motor rated current
All specified restarts have been used
Motor is running in the forward direction
Motor is running in the reverse direction
MSC-3 is enabled
I2t thermal motor overload has activated
MSC-3 is too hot for safe operation
Motor load is above the preset characteristic line
Energise the Line Contactor to charge the MSC-3 power circuits
The reading from the standard analogue input is above G025 HiCMP Level
The reading from the standard analogue input is below G026 LoCMP Level
The analogue input (left extended features card) is above G105 HiCMP Level
The analogue input (left extended features card) is below G106 LoCMP Level
The analogue input (right extended features card) is above G145 HiCMP Level
The analogue input (right extended features card) is below G146 LoCMP Level
The output of timer 1
The output of timer 2
G030 RL1 Signal
> RUN
(See the list for Relay Output Functions)