G025 Hi Compare Level; G026 Locmp Level - Zener MSC-3 Instruction Manual

Speed controllers
Hide thumbs Also See for MSC-3:
Table of Contents

Advertisement

• Press ESC to abandon the value change.
Regardless of how the analogue input is configured the maximum reference for input spanning is
determined by this parameter. The G024 Ref @MAX in parameter corresponds to the G022 MAX input
to define the input spanning configuration. See the Analogue Inputs and Spanning feature for details.

G025 Hi Compare Level

Range: 0.0...10.0 V or 0.0 to 20 mA
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
If the G020 Input Type is configured for > Volts then G025 Hi Compare Level will be displayed with
units of volts (V) otherwise G025 Hi Compare Level will be displayed with units of milliamps (mA). In
either case the high level compare threshold is determined by this parameter. When the input rises
above this level, the compare output will be true (high). See the Analogue Inputs and Spanning feature
for details.

G026 LoCMP Level

Range: 0.0...10.0 V or 0.0 to 20 mA
• Press  to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press  to accept the new value OR
• Press ESC to abandon the value change.
G025 Hi Compare
Level:
8.0V
G026 Lo Compare
Level:
2.0V
IM00120
IM00120
MSC-3 Instruction Manual
97