STEP 4
Follow the instructions on page 47 for MSC-3 startup, setting the parameters
according to the table below. Alternate values may be used to suit the application.
Menu
Menu Item
G00 INPUT/OUTPUT
G01 Inpt fxn CFG
(Input terminal
configuration)
G00 INPUT/OUTPUT
G03 RL1
G04 Rl2
B00 MOTOR
B01 MOTOR VOLTS
B02 MOTOR AMPS
B03 MOTOR HZ
B04 MOTOR RPM
D00 PROTECTION
D01 CURRENT LIM
D02 I2t Thermal overload
E00 STOP/START
E03 AUTO RESTART
E04 Reset by PF
F00 REFERENCES
F03 ESO REF
F10 PRESETS
H00PID Control
H06 SV Choice
H07 PV Choice
C00 PERFORMANCE
C03 RAMP
STEP 5
Now connect the wire to terminal 6.
End of procedure
Suggested Setting
I02 ~STOP = D1(2)
I00 FWD & LATCH = D2(3)
I08 ESO = D3(4)
I11 REMOTE = D4(5)
G030 RL1 Signal = RUN (default)
G040 RL2 Signal = TRIP (default)
Motor nameplate voltage
Motor nameplate amps
Motor nameplate frequency
Motor nameplate RPM
Motor nameplate current +10%
Motor nameplate current
E030 ARs ALLOWED = 5
ENABLED
PID OUTPUT
F100 PRESET 1
Set to % of transducer full scale equivalent to required pressure
F100 Preset 1
AI(32,34)
C030 ACCEL TIME = 10 sec
C031 DECEL TIME = 10 sec
C034 ESO RAMP = 10 sec
IM00120
IM00120
MSC-3 Instruction Manual