Setting Examples - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 12
Monitoring
12.4.4
290
Magnitude
% of In
compensation
+10
IMagComp5
IMagComp30
IMagComp100
5
-10
Angle
Degrees
compensation
+10
IAngComp30
IAngComp5
IAngComp100
5
-10
ANSI05000652 V3 EN
Figure 132:
Calibration curves

Setting examples

Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
Measurement function (CVMMXN) application for a 380kV OHL
Measurement function (CVMMXN) application on the secondary side of a
transformer
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values will
be provided.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
30
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
30
1MRK 511 286-UUS A
Measured
current
100
% of In
Measured
current
100
% of In
ANSI05000652_3_en.vsd
Application manual

Advertisement

Table of Contents
loading

Table of Contents