Application manual
The solution in figure
83
application example in figure 84.
IED
IED
. . .
IEC09000260 V2 EN
Figure 84:
Application principle for an alternative reservation solution
Bay control (QCBAY)
The Bay control (QCBAY) is used to handle the selection of the operator place for the bay.
The function gives permission to operate from two types of locations either from Remote
(for example, control centre or station HMI) or from Local (local HMI on the IED) or from
all (Local and Remote). The Local/Remote switch position can also be set to Off, which
means no operator place selected that is, operation is not possible neither from local nor
from remote.
QCBAY also provides blocking functions that can be distributed to different apparatuses
within the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
The function does not have a corresponding functionality defined in the IEC 61850
standard, which means that this function is included as a vendor specific logical node.
can also be realized over the station bus according to the
SCSWI
RES_EXT
SELECTED
GOOSEINTLKRCV
Other SCSWI in the bay to SELGGIO
RESGRANT
Section 10
Control
SELGGIO
SELECT1
OR
Station bus
IEC09000260_2_en.vsd