function as well as different time delay characteristics. It is important to base the
setting on fault calculations considering different operational states as well as time
delay coordination with other protections in the system.
Failure of the circuit beaker to interrupt fault current after protection trip. The breaker
failure protection function is essential in a protection system using local redundancy.

Bus coupler in a high impedance grounded network

Normally the following fault scenarios require back-up protection functions:
Short circuits on one of the busbar sections and short circuits on outgoing lines. For
these faults the four step phase overcurrent protection should be used. The four step
phase overcurrent protection has the possibility of directional function as well as
different time delay characteristics. It is important to base the setting on fault
calculations considering different operational states as well as time delay co-
ordination with other protections in the system.
Phase-to-ground faults. In high impedance grounded networks the fault current at a
single phase-to-ground fault is small. For these faults the sensitive residual
overcurrent protection should be used. The sensitive residual overcurrent protection
has the possibility of directional function. It is important to base the setting on fault
calculations considering different operational states as well as time delay co-
ordination with other protections in the system. As a second protection a residual
voltage protection is often used.
Failure of the circuit beaker to interrupt fault current after protection trip. The breaker
failure protection function is essential in a protection system using local redundancy.
The recommendations in table
Enabled: It is recommended to have the function activated in the application
Disabled: It is recommended to have the function deactivated in the application
Application dependent.: The decision to have the function activated or not is
dependent on the specific conditions in each case
Application 3 and Application 4 in table
examples given in previous sections.