ABB REC650 Applications Manual page 325

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 286-UUS A
Application manual
IEC08000174 V1 EN
Figure 142:
SMT: GOOSE marshalling with SMT
GOOSE receive function blocks extract process information, received by the data set, into
single attribute information that can be used within the application configuration. Crosses
in the SMT matrix connect received values to the respective function block signal in SMT,
see
Figure 143
The corresponding quality attribute is automatically connected by SMT.
This quality attribute is available in ACT, through the outputs of the
available GOOSE function blocks.
Section 14
Station communication
IEC08000174.vsd