During the tIntermediate time the position indication is allowed to be in an intermediate
(00) state. When the time has expired, the switch function is reset. The indication of the
mid-position at SCSWI is suppressed during this time period when the position changes
from open to close or vice-versa.
If the parameter AdaptivePulse is set to Adaptive the command output pulse resets when
a new correct end position is reached. If the parameter is set to Not adaptive the command
output pulse remains active until the timer tOpenPulsetClosePulse has elapsed.
tOpenPulse is the output pulse length for an open command. The default length is set to
200 ms for a circuit breaker (SXCBR) and 200 ms for a disconnector or grounding switch
(SXSWI).
tClosePulse is the output pulse length for a close command. The default length is set to 200
ms for a circuit breaker (SXCBR) and 200 ms for a disconnector or grounding switch
(SXSWI).
SuppressMidPos when Enabled will suppress the mid-position during the time
tIntermediate.
SwitchType is an enumeration according to IEC 61850-7-4 to indicate the switch type
assigned to SXSWI

Bay control (QCBAY)

If the parameter AllPSTOValid is set to No priority, all originators from local and remote
are accepted without any priority.
Interlocking
Identification
Function description
Logical node for interlocking
Interlocking for busbar grounding switch
Interlocking for bus-section breaker
Interlocking for bus-section
disconnector
Interlocking for bus-coupler bay
Interlocking for 1 1/2 breaker diameter
Interlocking for 1 1/2 breaker diameter
Table continues on next page
IEC 61850
IEC 60617
identification
identification
SCILO
-
BB_ES
-
A1A2_BS
-
A1A2_DC
-
ABC_BC
-
BH_CONN
-
BH_LINE_A
-
1MRK 511 286-UUS A
ANSI/IEEE C37.2
device number
3
3
3
3
3
3
3
Application manual

Advertisement

Table of Contents
loading

Table of Contents