ABB REC650 Applications Manual page 40

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 2
Application
Table 1:
Functionality table
Function
Instantaneous phase overcurrent protection ,
3-phase output PHPIOC (50)
Four step phase overcurrent protection, 3-
phase output OC4PTOC (51_67)
Instantaneous residual overcurrent
protection EFPIOC(50N)
Four step residual overcurrent protection
EF4PTOC (51N_67N)
Sensitive directional residual overcurrent and
power protection SDEPSDE (67N)
Thermal overload protection, one time
constant, Fahrenheit LFPTTR/LCPTTR (26)
Fahrenheit/Celsius
Application dependent
Breaker failure protection, 3-phase activation
and output CCRBRF (50BF)
Pole discordance protection CCRPLD (52PD)
Broken conductor check BRCPTOC (46)
Directional under-power protection
GUPPDUP (37)
Table continues on next page
34
calculations considering different operational states as well as time delay co-
ordination with other protections in the system. As a second protection a residual
voltage protection is often used.
Failure of the circuit beaker to interrupt fault current after protection trip. The breaker
failure protection function is essential in a protection system using local redundancy.
Autoreclosing is normally used on power lines as most faults are transient, that is the
arcing fault will extinguish after a short zero voltage interval.
The recommendations in table
Enabled: It is recommended to have the function activated in the application
Disabled: It is recommended to have the function deactivated in the application
Application dependent : The decision to have the function activated or not is
dependent on the specific conditions in each case
Application 1 and Application 2 in table
examples given in previous sections.
Application 1
Enabled
Enabled
Enabled
Enabled
Disabled
Application dependent
Enabled
Application dependent
Application dependent
Application dependent
1
have the following meaning:
Application 2
Enabled
Enabled
Disabled
Disabled
Enabled
Application dependent
Enabled
Application dependent
Application dependent
Application dependent
1MRK 511 286-UUS A
1
are according to application
Application manual