Iec61850-8-1 Communication Protocol - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 286-UUS A
Section 14
14.1
14.1.1
14.1.2
Application manual
Station communication

IEC61850-8-1 communication protocol

Identification
Function description
IEC 61850-8-1 communication protocol
Application
IEC 61850-8-1 communication protocol allows vertical communication to HSI clients
and allows horizontal communication between two or more intelligent electronic devices
(IEDs) from one or several vendors to exchange information and to use it in the
performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1
standard, allows the IEDs to communicate state and control information amongst
themselves, using a publish-subscribe mechanism. That is, upon detecting an event, the
IED(s) use a multi-cast transmission to notify those devices that have registered to receive
the data. An IED can, by publishing a GOOSE message, report its status. It can also
request a control action to be directed at any device in the network.
Figure 139
shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1
specifies only the interface to the substation LAN. The LAN itself is left to the system
integrator.
Station communication
IEC 61850
IEC 60617
identification
identification
IEC 61850-8-1
-
Section 14
ANSI/IEEE C37.2
device number
-
315