Setting Guidelines - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 286-UUS A
11.1.3
11.2
11.2.1
11.2.2
11.2.3
Application manual

Setting guidelines

The parameters for Tripping logic common 3-phase output SMPPTRC (94) are set via the
local HMI or through the Protection and Control Manager (PCM600).
The following trip parameters can be set to regulate tripping.
Operation: Sets the mode of operation. Disabled switches the function off. The normal
selection is Enabled.
TripLockout: Sets the scheme for lock-out. Disabled only activates the lock-out output.
Enabled activates the lock-out output and latches the output TRIP. The normal selection
is Disabled.
AutoLock: Sets the scheme for lock-out. Disabled only activates lock-out through the
input SETLKOUT. Enabled additonally allows activation through the trip function itself.
The normal selection is Disabled.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to ensure
that the breaker is tripped correctly. Normal setting is 0.150s.
Trip matrix logic TMAGGIO
Identification
Function description
Trip matrix logic
Application
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route trip
signals and other logical output signals to the tripping logics SMPPTRC and SPTPTRC
or to different output contacts on the IED.
TMAGGIO 3 output signals and the physical outputs allows the user to adapt the signals
to the physical tripping outputs according to the specific application needs for settable
pulse or steady output.
Setting guidelines
Operation: Turns the operation of the function Enabled/Disabled.
IEC 61850
IEC 60617
identification
identification
TMAGGIO
-
Section 11
Logic
ANSI/IEEE C37.2
device number
-
271