Section 6
Current protection
6.4.3.3
6.4.3.4
112
protection. The maximum ground-fault current at the local source can be used to calculate
the value of ZN as V/(√3 · 3I
is set. Setting is in primary ohms.
When the dual polarizing method is used it is important that the product INx>· ZNpol is
not greater than 3V
. If so, there is a risk for incorrect operation for faults in the reverse
0
direction.
IPolMin: is the minimum ground-fault current accepted for directional evaluation. For
smaller currents than this value the operation will be blocked. Typical setting is 5-10% of
IBase.
VPolMin: Minimum polarization (reference) residual voltage for the directional function,
given in % of VBase/√3.
IDirPU: Operate residual current release level in % of IBase for directional comparison
scheme. The setting is given in % of IBase and must be set below the lowest INx> setting,
set for the directional measurement. The output signals, PUFW and PUREV can be used
in a teleprotection scheme. The appropriate signal should be configured to the
communication scheme block.

2nd harmonic restrain

If a power transformer is energized there is a risk that the current transformer core will
saturate during part of the period, resulting in a transformer inrush current. This will give
a declining residual current in the network, as the inrush current is deviating between the
phases. There is a risk that the residual overcurrent function will give an unwanted trip.
The inrush current has a relatively large ratio of 2nd harmonic component. This
component can be used to create a restrain signal to prevent this unwanted function.
At current transformer saturation a false residual current can be measured by the
protection. Also here the 2
2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2nd
harmonic restrain signal. The setting is given in % of the fundamental frequency residual
current.
HarmRestrainx: Enable block of step x from the harmonic restrain function.
Line application example1
The Four step residual overcurrent protection EF4PTOC (51N/67N) can be used in
different ways. Below is described one application possibility to be used in meshed and
effectively grounded systems.
) Typically, the minimum ZNPol (3 · zero sequence source)
0
nd
harmonic restrain can prevent unwanted operation.
1MRK 511 286-UUS A
Application manual