Automatic Continuation Of The Reclosing Sequence - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 286-UUS A
10.2.2.13
10.2.2.14
10.2.3
10.2.3.1
Application manual
SMBRREC (79)
BU-TRIP
OR
INHIBIT
ZCVPSOF-TRIP
UNSUCCL
CCRBRF (50BF)
SOFTWARE
OR IO RESET
TRBU
MAN CLOSE
SMBRREC (79) CLOSE
SESRSYN (25)
AUTOSTOP
MANENOK
ANSI11000167 V1 EN
Figure 78:
Lock-out arranged with internal logic with manual closing going through
in IED

Automatic continuation of the reclosing sequence

SMBRREC (79) function can be programmed to proceed to the following reclosing shots
(if multiple shots are selected) even if start signals are not received from the protection
functions, but the breaker is still not closed. This is done by setting parameter AutoCont =
Enabled and tAutoContWait to the required delay for the function to proceed without a
new start.
Thermal overload protection holding the auto-reclosing function back
If the input THOLHOLD (thermal overload protection holding reclosing back) is
activated, it will keep the reclosing function on a hold until it is reset. There may thus be
a considerable delay between start of Auto-Reclosing and reclosing command to the
circuit-breaker. An external logic limiting the time and sending an inhibit to the INHIBIT
input can be used. The input can also be used to set the Auto-Reclosing on hold for a longer
or shorter period.
Setting guidelines
Configuration
Use the PCM600 configuration tool to configure signals.
SMPPTRC (94)
OR
SETLKOUT
CLLKOUT
RESET LOCK-OUT
RSTLKOUT
OR
OR
Section 10
Control
AND
CLOSE COMMAND
ANSI11000167_1_en.vsd
205