Configuration Setting - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 10
Control
10.4.8.2
252
189
152
689
BH_LINE_A
989
989G
ANSI04000513 V1 EN
Figure 118:
Switchyard layout breaker-and-a-half
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.

Configuration setting

For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE
and 1=TRUE:
989_OP = 1
989_CL = 0
189G
289G
389G
6189
6289
152
289G
189G
BH_CONN
1MRK 511 286-UUS A
WA1 (A)
WA2 (B)
289
189G
152
289G
689
389G
BH_LINE_B
989
989G
en04000513_ansi.vsd