Section 10
Control
10.1.3.1
190
The SESRSYN and connected SMAI function block instances must have
the same cycle time in the application configuration.

Single circuit breaker with single busbar

Bus 1
189
Fuse
VT
BKR1
52
Line
ANSI11000164 V2 EN
Figure 73:
Connection of SESRSYN (25) function block in a single busbar
arrangement
Figure
73
illustrates connection principles. For the SESRSYN (25) function there is one
voltage transformer on each side of the circuit breaker. The voltage transformer circuit
connections are straightforward; no special voltage selection is necessary.
The voltage from busbar VT is connected to V3PB1 and the voltage from the line VT is
connected to V3PL1. The positions of the VT fuses shall also be connected as shown
above. The voltage selection parameter CBConfig is set to No voltage sel.
SMAI
VBus
SMAI
VLine
Fuse
VT
1MRK 511 286-UUS A
SESRSYN (25)
V3PB1*
SYNOK
GRP_OFF
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
LINE1_CL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
FRDIFSYN
VB1FF
FRDERIVA
VB2OK
VOKSC
VB2FF
VDIFFSC
VL1OK
FRDIFFA
VL1FF
PHDIFFA
VL2OK
FRDIFFM
VL2FF
PHDIFFM
STARTSYN
INADVCLS
TSTSYNCH
VDIFFME
TSTSC
FRDIFFME
TSTENERG
PHDIFFME
AENMODE
MENMODE
MODEAEN
MODEMEN
ANSI11000164_2_en.vsd
Application manual
L1SEL
L2SEL
Vbus
VLine