14.6
Application manual

Setting guidelines

The redundant station bus communication is configured using the local HMI, Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
The settings can be viewed and OperationMode can be set in the Parameter Setting tool in
PCM600 under IED Configuration/Communication/TCP-IP configuration/
ETHLAN1_AB where
OperationMode can be set to Off, NonRedundant(A) or PRP(A+B). The redundant
communication will be activated when this parameter is set to PRP(A+B).
The ETHLAN1_AB in the Parameter Setting tool is relevant only when the COM03
module is present.
IEC13000009 V1 EN
Figure 145:
PRP1 Configured in the Parameter Setting tool
IEC13000010 V1 EN
Figure 146:
Lock/Unlock parameter
Station communication
IEC13000009-1-en.vsd
IEC13000010-1-en.vsd
Section 14
323