Auto-Recloser Parameter Settings - ABB REC650 Applications Manual

Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 286-UUS A
10.2.3.2
Application manual
BIO
INPUT
xx
xx
xx
xx
xx
xx
xx
xx
xx
PROTECTION
xxxx-TRIP
OR
ZCVPSOF-TRIP
OR
ZQMPDIS(21)--TRIP
SESRSYN (25)-AUTOOK
ANSI10000193 V2 EN
Figure 79:
Example of I/O-signal connections at a three-phase reclosing function

Auto-recloser parameter settings

The operation of the Autorecloser for 3-phase operation (SMBRREC ,79) function can be
switched Enabled and Disabled. The setting makes it possible to switch it Enabled or
Disabled using an external switch via IO or communication ports.
, Number of reclosing shots
In sub-transmission 1 shot is mostly used. In most cases one reclosing shot is sufficient as
the majority of arcing faults will cease after the first reclosing shot. In power systems with
many other types of faults caused by other phenomena, for example wind, a greater
number of reclose attempts (shots) can be motivated.