The formula for mains voltage unbalance is:
(Most deviating line-to-line voltage - average voltage)*100/average voltage (nominal value in %)
Prior to closing a breaker, the unit checks that the phase sequence is correct, depending on the
chosen phase direction in parameter 2280: "phase rotation". If it is incorrect (reversed), an alarm
will be issued and the breaker in question (generator or option B3 mains breaker) will not be
closed and the breaker's LED will flash red.
It is possible to configure the inputs indicated in the table. The unit has a number of passive
binary inputs (input terminals 10 to 15).
Input function
Alarm acknowledge
Start enable (OFF = start blocked)
Remote start/stop
Access lock
Remote manual/auto
Fire pump (shutdown override)
D+ (digital running feedback)
Idle speed
Test sequence
GB Pos on
GB Pos off
Digital inputs no. 1 to 6 used as alarms
Inhibit EI alarms
Remote Start (pulse)
Remote Stop (pulse)
Remote Start and close (pulse)
Remote Open and stop (pulse)
EIC increase speed
EIC decrease speed
Remote GB open
Remote GB close
Island mode
GB close inhibit
Input function description
1. Alarm acknowledge
Acknowledges all present alarms.
2. Start enable
This input must be activated to start the engine.
3. Remote start/stop input
Activating this input will start the genset. Deactivating it will stop the genset after cool down
(auto mode only).
4. Access lock
Activating the access lock input deactivates the control push-buttons on the display and the
possibility to change parameters. It will be possible to view measurements, alarms and the
log.
DEIF A/S

Mains voltage unbalance detection

Phase sequence error

Utility software input configuration

Installation Instructions and Reference Handbook
Comment
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable (option G6)
Configurable (option G6)
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Page 35 of 123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents