GC-1F
Technical specifications
Accuracy:
Operating temp.:
Storage temp.:
Heat foil (option L2):
Measuring input voltage:
Load:
Frequency:
Measuring input current:
Current overload:
Short-circuit protection:
Consumpt. max.:
Pickup input voltage:
Frequency:
Aux. supply:
Passive binary input
voltage:
Impedance:
Dropout cranking:
VDO inputs:
Analogue input:
Input impedance:
DEIF A/S

Technical information

Class 2.0
To IEC/EN 60688
-20 to 70 °C (-4 to 158 °F)
(UL/cUL Listed: Max. 50 °C ambient)
-40 to 70 °C (-40 to 158 °F)
Display will operate at -40 °C (-40 °F)
50 to 480 V AC (+20 %)
Phase to phase
1.5 M/phase
30 to 70 Hz
1A or 5 A AC from current transformer
(UL/cUL Listed: Use listed or R/C (XODW2.8) current transfor-
mers
4 × In continuously
20 × In, 10 s (max. 75 A)
80 × In, 1 s (max. 250 A)
3 % of 350 %*In (only HW 1.05 and 2.0x.x)
0.3 VA/phase
2 to 70 V peak
10 to 10000 Hz
6 to 36 V DC continuously
(UL/cUL Listed: 7.5 to 32.7 V DC)
Max. 8 W consumption
With L2 heatfoil, max. 16 W
Bi-directional optocoupler
6 to 36 V DC
4.7 k
Able to survive 0 V for 50 ms at
12 V DC aux. supply before dropout
Resistor inputs 0-2500 ohm, internal 3 V supply
(0)4 to 20 mA from active transducer
50 