Vdo Sensors - Deif GC-1F Installation Instructions Manual

Genset controller
Hide thumbs Also See for GC-1F:
Table of Contents

Advertisement

GC-1F
VDO sensors are noise sensitive, therefore we recommend to use 2-wire sensors.
There are three VDO inputs in the unit. The inputs have different functions due to the fact that
the hardware design is able to cover several VDO types.
All VDO inputs have a general accuracy of 2 %.
VDO input 2:
VDO input 3:
VDO input 1:
HW 1.05 and SW 2x.x have max. 2500 Ohm of all VDO sensors.
VDO input 1, fuel level
Value
0 %
100 %
Value
0 %
100 %
VDO input 1, fuel level: type 1 and 2 curves are linear.
Type 3 is fully configurable with eight points in the input range 0 to 180  and 0
to 100 %.
DEIF A/S

VDO sensors

Oil pressure - max. 240 Ohm
Cooling water temperature - max. 2500 Ohm
Fuel level sensor - max. 180 Ohm
VDO sensor type
Type 1
Resistance
78.8 
1.6 
VDO sensor type
Type 2
Resistance
3 
180 
Value
%
0
10
20
30
40
50
60
70
80
90
100
Installation Instructions and Reference Handbook
VDO sensor type
Type 3
Resistance
Configurable