Parameter List; Parameter Groups; Setup - Deif GC-1F Installation Instructions Manual

Genset controller
Hide thumbs Also See for GC-1F:
Table of Contents

Advertisement

GC-1F
This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to
be used for reference when information about specific parameters is needed.
In the parameter overview, the parameters are divided into three parameter groups. The
parameter groups can be enabled and disabled in the parameters 6950 to 6970. If a parameter
group is enabled, the parameters will be accessible from the display of the GC-1F. To see the
specific parameter, refer to the parameter list. If for example a parameter is marked (P2), it is
available from the display, if parameter group 2 is enabled. The default display parameter setting
is the parameter setting that will always be present in the display parameter list. These
parameters are marked with a *.
The setup of parameters is performed via the display or the PC utility software (USW).
Therefore, the default settings can be changed to the relevant settings through the utility
software or by means of the push-buttons on the display.
The settings can be entered through the setup menu. If no entry has taken place before, then
the first display to appear is the password display. Enter the factory setting password to gain
access to the menus.
The factory customer password is 2000. The factory service password is 2001.
If no action has been taken after 30 seconds, then the password entry will be deactivated, and a
new password entry is needed. (If entry via the USW is used, the password is only needed once
per connection).
Each parameter description is structured according to the same principles. Under the parameter
title heading, the detailed parameter descriptions are illustrated and presented. First, a table
indicating the parameter facts related to the individual parameter title is presented:
Channel
Para-
meter
number
title
indicated in
USW
4310 VDO input – oil pressure 2.x
No.
Setting
4311
Oil pressure 2.1
4312
Oil pressure 2.1
4313
Oil pressure 2.1
4314
Oil pressure 2.1
4315
Oil pressure 2.1
4316
Oil pressure 2.1
DEIF A/S

7. Parameter list

Parameter groups

Setup

Changeable
settings
Min. setting
Set point
0.0 bar
Delay
0.0 s
Output A
R0 (none)
Output B
R0 (none)
Enable
OFF
Fail class
Warning
Installation Instructions and Reference Handbook
Min. - max. set
points
Max. setting
10.0 bar
100.0 s
R26 (relay 26)
R26 (relay 26)
ON
Shutdown
Default set point
from factory
Factory
setting
4.0 bar
5.0 s
R0 (none)
R0 (none)
OFF
Trip of GB
Page 87 of 123