Analogue Inputs 0(4) To 20 Ma; Analogue Input 0(4) To 20 Ma - Deif GC-1F Installation Instructions Manual

Genset controller
Hide thumbs Also See for GC-1F:
Table of Contents

Advertisement

GC-1F
The scaling of the 0(4) to 20 mA inputs for correct display reading can only be done via the PC
utility software.
4 to 20 mA inputs have wire break function. Wire break alarm will be active when
current goes below 2.5 mA. It is not possible to disable the wire break function.
4120 0-20 4-20 mA 1.1
No.
Setting
4121
0(4)-20 mA 1.1
4122
0(4)-20 mA 1.1
4123
0(4)-20 mA 1.1
4124
0(4)-20 mA 1.1
4125
0(4)-20 mA 1.1
4126
0(4)-20 mA 1.1
4130 0-20 4-20 mA 1.2
No.
Setting
4131
0(4)-20 mA 1.2
4132
0(4)-20 mA 1.2
4133
0(4)-20 mA 1.2
4134
0(4)-20 mA 1.2
4135
0(4)-20 mA 1.2
4136
0(4)-20 mA 1.2
4250 0-20 4-20 mA 2.1
No.
Setting
4251
0(4)-20 mA 2.1
4252
0(4)-20 mA 2.1
4253
0(4)-20 mA 2.1
4254
0(4)-20 mA 2.1
4255
0(4)-20 mA 2.1
4256
0(4)-20 mA 2.1
4260 0-20 4-20 mA 2.2
No.
Setting
4261
0(4)-20 mA 2.2
4262
0(4)-20 mA 2.2
4263
0(4)-20 mA 2.2
4264
0(4)-20 mA 2.2
4265
0(4)-20 mA 2.2
4266
0(4)-20 mA 2.2
4380 0-20 4-20 mA 3.1
No.
Setting
4381
0(4)-20 mA 3.1
4382
0(4)-20 mA 3.1
4383
0(4)-20 mA 3.1
4384
0(4)-20 mA 3.1
4385
0(4)-20 mA 3.1
4386
0(4)-20 mA 3.1
DEIF A/S

Analogue inputs 0(4) to 20 mA

Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Installation Instructions and Reference Handbook
Min. setting
Max. setting
4 mA
20 mA
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
4 mA
20 mA
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
4 mA
20 mA
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
4 mA
20 mA
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
4 mA
20 mA
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Factory
setting
10 mA
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
10 mA
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
10 mA
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
10 mA
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
10 mA
5.0 s
R0 (none)
R0 (none)
OFF
Page 102 of 123