Rpm Input - Deif GC-1F Installation Instructions Manual

Genset controller
Hide thumbs Also See for GC-1F:
Table of Contents

Advertisement

GC-1F
4460 VDO water temp. input 3.1
No.
Setting
4461
VDO 3.1
4462
VDO 3.1
4463
VDO 3.1
4464
VDO 3.1
4465
VDO 3.1
4466
VDO 3.1
4470 VDO water temp. input 3.2
No.
Setting
4471
VDO 3.2
4472
VDO 3.2
4473
VDO 3.2
4474
VDO 3.2
4475
VDO 3.2
4476
VDO 3.2
4630 VDO low coolant temp. input 3.3
No.
Setting
4631
VDO 3.3
4632
VDO 3.3
4633
VDO 3.3
4634
VDO 3.3
4635
VDO 3.3
4636
VDO 3.3
VDO type: See functional description.
4510 Overspeed 1 (RPM input)
No.
Setting
4511
Overspeed 1
4512
Overspeed 1
4513
Overspeed 1
4514
Overspeed 1
4515
Overspeed 1
4516
Overspeed 1
4520 Overspeed 2 (RPM input)
No.
Setting
4521
Overspeed 2
4522
Overspeed 2
4523
Overspeed 2
4524
Overspeed 2
4525
Overspeed 2
4526
Overspeed 2
Overspeed 1 and 2 are always active if enabled regardless of nominal setting.
Thus it is possible to set two levels of overspeed.
DEIF A/S
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class
Set point
Delay
Output A
Output B
Enable
Fail class

RPM input

Set point
Timer
Relay output A
Relay output B
Enable
Fail class
Set point
Timer
Relay output A
Relay output B
Enable
Fail class
Installation Instructions and Reference Handbook
Min. setting
Max. setting
0 °C
150 °C
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0 °C
150 °C
0.0 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
-50 °C
410 °C
0.0 s
10.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0 %
400 %
0.2 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Min. setting
Max. setting
0 %
400 %
0.2 s
100.0 s
R0 (none)
R26 (relay 26)
R0 (none)
R26 (relay 26)
OFF
ON
See description of fail classes
Factory
setting
95 °C
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
95 °C
5.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
10 °C
1.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
110 %
15.0 s
R0 (none)
R0 (none)
OFF
Factory
setting
110 %
15.0 s
R0 (none)
R0 (none)
OFF
Page 104 of 123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents