Parameter Overview - Deif GC-1F Installation Instructions Manual

Genset controller
Hide thumbs Also See for GC-1F:
Table of Contents

Advertisement

GC-1F
Parameter group 1 (Disp. view settings)
6181 Start prepare
6183 Start On time
6184 Start Off time
6211 Cool-down
6212 Extended stop
Parameter group 2 (Disp. view settings)
1030 Over-current 1: Delay + Set point
1040 Over-current 2: Delay + Set point
1130 Gen short circuit 1 Delay + Set point
1140 Gen short circuit 2 Delay + Set point
1150 Over-voltage 1: Delay + Set point
1160 Over-voltage 2: Delay + Set point
1170 Under-voltage 1: Delay + Set point
1180 Under-voltage 2: Delay + Set point
1210 Over-frequency 1: Delay + Set point
1220 Over-frequency 2: Delay + Set point
1240 Under-frequency 1: Delay + Set point
1250 Under-frequency 2: Delay + Set point
1450 Overload 1: Delay + Set point
1460 Overload 2: Delay + Set point
Parameter group 3 (Disp. view settings)
4220 Fuel 1.1: Delay + Set point*
4230 Fuel 1.2: Delay + Set point*
4620 Fuel 1.3: Delay + Set point*
4600 V-belt: Delay
4610 Charger gen: Delay
6350 D+: Delay
6550 Fuel pump: Delay*
6551 Fuel pump 1: Set point*
6552 Fuel pump 2: Set point*
* Only shown if multi-input 1 is set to VDO
Always shown parameters in display
1985 Ext. run fb. fail
4560 Hz/V failure timer
4580 Stop fail
4960 Battery low 1: Delay + Set point
4970 Battery High: Delay + Set point
6070 Genset mode (B3)
6101 Running time
6103 Number of GB operations
6104 Number of MB operations (B3)
6105 kWh reset
6112 Service timer 1: Hours
6113 Service timer 1: Days
6116 Service timer 1: Reset
6122 Service timer 2: Hours
DEIF A/S
Installation Instructions and Reference Handbook

Parameter overview

6123 Service timer 2: Days
6126 Service timer 2: Reset
6130 Alarm horn
6221 Hz/V OK timer
6222 Hz/V OK voltage
6223 Hz/V OK frequency
6901 Alarm jump
7041 AMF test time (B3)
7062 Mains OK U (B3)
7065 Mains failure U low (B3)
7066 Mains failure U high (B3)
7072 Mains OK f (B3)
7075 Mains failure f low (B3)
7076 Mains failure f high (B3)
7091 Island test time
7513 Service mode (RTU/ASCII)
7560 Engine I/F
7565 EIC Auto view (H5)
9151 Backlight dimmer
Hour adjust. ( "Sync. clock" to PC button)
Minutes adjust. ( "Sync. Clock" to PC button)
Seconds Adjust.( "Sync. Clock" to PC button)
Date adjust ( "Sync. Clock" to PC button)
Month adjust ( "Sync. Clock" to PC button)
Year adjust ( "Sync. Clock" to PC button)
Parameters only configurable from USW
1000 Reverse power
1620 Mains voltage unbalance
2150 Phase sequence error
2200-2210 MB control
2280 Phase rotation
2160-2170 GB control
2770 EIC control
3000-3050 Digital input term. 10-15
3490 Emergency stop
3400...3420 Binary multi-input settings
4120...4390 mA input settings
4310...4470 VDO multi-input settings
4510 Gen. overspeed 1
4520 Gen. overspeed 2
4580 Stop fail
4630 Low water temp.
4950 Battery low 2
5000...5060 Relay functions
6001...6005 Nominal settings 1
6006 Enable nom. Settings
6011...6015 Nominal settings 2
Page 89 of 123