Fail class:

When the alarm occurs, the unit will react depending on the selected fail class.
Small differences due to the character of the parameters may exist between the
individual tables.
The fail class settings for the protections have the following possibilities:
Value
0: Warning
1: Trip
2: Trip and stop
3: Shutdown
4: Shutdown + Manual mode
DEIF A/S
Installation Instructions and Reference Handbook
Fail class
Comment
Shown in alarm pop-up window and activates the
chosen relays.
Shown in alarm pop-up window and activates the
chosen relays. Trips the breaker.
Shown in alarm pop-up window and activates the
chosen relays. Trips the breaker, cools down the
engine and stops it.
Shown in alarm pop-up window and activates the
chosen relays. Trips the breaker and shuts the engine
down immediately.
Same as "shutdown" but also change to Manual mode