Maintenance
Fire Suppression System Maintenance
Test
NOTE: Fire suppression system only available on
gas and steam models.
To ensure proper operation, the fire suppression
system must be tested every three months. If the
system test does not perform as indicated:
1. Discontinue use of the tumble dryer.
2. Refer to Troubleshooting Manual or contact a
qualified service person.
3. Restore the fire suppression system to proper
working order before using tumble dryer.
Create a maintenance record with a check box for
pass, the date and a signature. Store this record in an
area where it will not be damaged, but is easily
accessible to person performing tests.
NOTE: Failure to maintain the fire suppression
system will void the tumble dryer warranty.
NOTE: The auxiliary output is activated during the
fire suppression system maintenance test sequence.
Consider this fact prior to testing the system every
three months. (Example – If the external system
uses the auxiliary output to call the fire
department, inform the fire department before and
after the fire suppression system maintenance test.)
CAUTION
Clean up any water spilled during testing
to avoid personal injury.
90
W487
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
1
4
3
1
Opening for Auxiliary Alarm Cable
2
Test Button
3
Light
4
Reset Button
Figure 61
To perform the fire suppression system maintenance
test:
1. If the auxiliary alarm output is connected to a
separate alarm system, disconnect prior to
performing the fire suppression system
maintenance test.
2. Remove any lint from the lint compartment.
3. Ensure temperature sensors are free of lint.
4. Place a load of dry towels in the tumble dryer.
Refer to Table 18 for proper load size. Ensure the
cylinder baffles are to the left and right of the
spray manifold located at the center top of the
cylinder.
5. Unlock the fire suppression system control box.
6. Press and hold the test button, verify the light is
on, this should take approximately five seconds.
Refer to Figure 61. After a one-second pause
water should begin to spray into the cylinder.
7. After 15 seconds of water spray, press and hold
the reset button until water spray is off and light
is off. This should take approximately one
second. Refer to Figure 61 and Figure 62.
TMB1999N
2
TMB1999N
70457901ENR7